Low or no current from DC string
This article explains the possible causes when an inverter is producing / generating low or NO current in one or more of its DC inputs, despite measuring expected DC voltage
The open circuit voltage of the string should be much greater than the minimum input voltage of the inverter; if there are too few modules in series, the open circuit voltage of the string will be too low, resulting in no display on the inverter screen. Solution: Increase the number of solar panels in series.
Properly grounding your inverter is crucial to avoid voltage fluctuations. In conclusion, inverter low voltage problems are not uncommon, but with the right knowledge and approach, they can be resolved. By understanding the causes behind such issues and following the appropriate diagnostics, you can get your inverter back to working optimally.
Once you have identified the problem, you can begin troubleshooting it. Here are some steps to follow: Check the input voltage. The input voltage to the inverter should be within the specified range. If the input voltage is too low or too high, the inverter may not function properly. Check the output voltage and frequency.
Reason 3: The DC input voltage is too low. When the string output voltage is lower than the minimum input voltage of the inverter, there is no display on the inverter screen. To make sure, you can use a multimeter to measure the output voltage of the photovoltaic string to see whether the voltage reaches the minimum input voltage of the inverter.